Vol.14, No.1, February 2025. ISSN: 2217-8309 eISSN: 2217-8333
TEM Journal
TECHNOLOGY, EDUCATION, MANAGEMENT, INFORMATICS Association for Information Communication Technology Education and Science |
Dissolved Gas Analysis of Methyl Ester-Mineral Oil Mixture Under Partial Discharge
Abdul Rajab, Ardison Ardison, Rizki Wahyu Pratama, Riko Novendra, Baharuddin Baharuddin, Tri Artono
© 2025 Baharuddin Baharuddin, published by UIKTEN. This work is licensed under the Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 License. (CC BY-NC-ND 4.0)
Citation Information: TEM Journal. Volume 14, Issue 1, Pages 55-63, ISSN 2217-8309, DOI: 10.18421/TEM141-06, February 2025.
Received: 20 June 2024. Revised: 03 December 2024.
Abstract:
This paper deals with the dissolved gas analysis (DGA) of methyl ester and mineral oil mixtures under partial discharge (PD). Experiments were conducted on pure methyl ester and mixtures containing 5%, 7.5%, and 10% mineral oil to simulate transformer retrofilling conditions. PD was generated using a needle-plane electrode pair immersed in the oil sample and subjected to AC high voltage. The gases produced were analyzed using gas chromatography to evaluate gassing tendencies and fault diagnostics using the Key Gas, Duval Triangle, Duval Pentagon, and IEC 599 ratio methods. Results indicate that residual mineral oil reduces the partial discharge inception voltage (PDIV) and increases gas production. Hydrogen, constituting approximately 85% of total gas production, indicates the applicability of the Key Gas method. The Duval Triangle method consistently identified PD faults, whereas the Duval Pentagon method underestimated PD as stray gassing. In contrast, the IEC 599 method was ineffective for fault diagnosis in methyl ester-based oils under PD. These findings suggest that up to 10% residual mineral oil in a retrofilling scenario does not significantly affect DGA-based fault diagnostics in methyl ester but enhances gas production due to increased PD activity.
Keywords – DGA, fault identification, partial discharge, transformer retrofilling. |
|
----------------------------------------------------------------------------------------------------------- ----------------------------------------------------------------------------------------------------------- |